beautypg.com

Delta Electronics Human Machine Interface DOP-A Series User Manual

Page 173

background image

Chapter 3 Element Function|ScrEdit Software User Manual

3-36

Revision Apr. 30th, 2007, 2007PDD23000002

„

Day-of-week Display

Table 3.8.6 Property Description of Day-of-week Display Element

Property Description of Day-of-week Display Element

Display the day (Sunday ~ Monday) of the week. The state default setting of the Day-of-week display
element is set to 7. It indicates that there are 7 states for this element. The user can define the display text,
font and color for each day directly in the property table.

Text / Text Size
Font / Text Color

The user can set the text, text size, font and text color provided by Windows® to
determine the text display on the element. (Please refer to Table 3.2.2 Property
Description of General Buttons.)

Border Color
Background Color

(Please refer to Table 3.8.2 Property Description of Numeric Display Element.)

Style

(Please refer to Table 3.8.2 Property Description of Numeric Display Element.)

„

Prestored Message

Table 3.8.7 Property Description of Prestored Message Element

Property Description of Prestored Message Element

Display the state content of PLC corresponding contact or register directly. The user can set state number
and text for each state.

Read Address

The address can be internal memory or the controller address. (Please refer to Table
3.2.2 Property Description of General Buttons.)

Text / Text Size
Font / Text Color

The user can set the text, text size, font and text color provided by Windows® to
determine the text display on the element. (Please refer to Table 3.2.2 Property
Description of General Buttons.)

Border Color
Background Color

(Please refer to Table 3.8.2 Property Description of Numeric Display Element.)

Style

(Please refer to Table 3.8.2 Property Description of Numeric Display Element.)

Bit

It can have two states.

Word

It can have 256 states.

Data Type

LSB

It can have 16 states.

Data Format

It provides BCD, Signed Decimal, Unsigned Decimal and Hex four kinds of data
format to define the read memory content.

Add/Remove State

It is used to set the state numbers of prestored message element. If the data length of
the value is in Word, 1~256 states can be set. If the data length of the value is in LSB,
16 states can be set. If the data length of the value is in Bit, only 2 states can be set.

„

Moving Sign

Table 3.8.8 Property Description of Moving Sign Element

Property Description of Moving Sign Element

Moving sign is a sign that uses movement, lighting, or special display to depict and display the state content
of the corresponding contact or register. The user can determine the display of the moving sign by the
settings of the direction, moving points, and interval (ms) in the property table.

Read Address

The address can be internal memory or the controller address. (Please refer to Table
3.2.2 Property Description of General Buttons.)

This manual is related to the following products: