beautypg.com

Chapter 7 example explanation – Delta Electronics Human Machine Interface DOP-A Series User Manual

Page 284

background image

Revision Apr. 30th, 2007, 2007PDD23000002

7-1

Chapter 7 Example Explanation

Programming MACRO files

This is for reference only. But will help the user to understand the requirements of using the HMI for

controlling the VFD-E AC drive. This is a tool to help in learning how HMI programming is done.

Making a button to turn on the VFD-E AC drive

We recommend the user to use a set button for this. Most elements require an address, some a bit other’s a

word. The set button requires a bit setting.

Remember to compile at the end of the programming. If an error occurs it will be shown on the Output

section of the Screen.

It is assumed that a Delta display kit is being used but if not just an E Drive and HMI with a power source and

communication cable will be needed.

• To start, the user must first make a new file. See Fig. 7.1

• Open the Screen Edit program

• Select

New

• Select the type of DOP being used. In this case 8 inch color AE type is selected.

• Base Port controller is Delta Controller ASCII.

• Drive parameter’s must be set-up as follows:

09.00 = 2: Communication Address (1to 254)

09.01 = 3: Transmission Speed (38,400)

09.04 = 0: Communication Protocol (7,n, 2)

02.00 = 3: Source of First Master Frequency Command (RJ-45)

02.01 = 4: Source of First Operation Command (RS-485 Serial communication (RJ-45)

This is for communication to the drive via RS-485 communication.

This manual is related to the following products: