beautypg.com

Delta Electronics Human Machine Interface DOP-A Series User Manual

Page 260

background image

Chapter 4 Macro Function|ScrEdit Software User Manual

Revision Apr. 30th, 2007, 2007PDD23000002

4-39

$1001 = 3A00H

Set starting Bit. Because the value of high byte and low
byte will be exchanged when HMI sends command, even
though the starting Bit is 3A when sending data, it is
needed to input 3A00.

$1009 = 0A0DH

Set end Bit. Because the value of high byte and low byte
will be exchanged when HMI sends command, even
though the end Bit is 0D0A when sending data, it is
needed to input 0A0D.

$1500 = PUTCHARS($1001, 20, 500)

Start to send data from $1001, the data length is 20
bytes and the timeout setting is 500ms.

$1501 = GETCHARS($1121, 20, 500)

Receive the PLC response data after communication.
The received data is stored in $1121, the data length is
20 bytes and the timeout setting is 500ms.

$1050 = B2W($1125, 6)

Decompose received ACSII code into one BYTE and
one BYTE from $1125 respectively and convert them
into WORD format.

$1060 = A2H($1051)

Then, start to convert the WORD data into the value in
hexadecimal format from $1051 and display the result in
decimal format on the screen.

„

Others

Command

Equation

Descrption

TIMETICK

V1 = TIMETICK

Get the time from system startup to
present

GETLASSERROR

V1 = GETLASTERROR

Get last error value

#

#V1

Comment

delay

delay V1

System delay

GETSYSTEMTIME

V1 = GETSYSTEMTIME

Get system time