ICNV

Convert floating point value to integer

Equation: V1= ICNV (V2) (Signed DW)

Convert floating point value or integer in V2 to integer and store in V1.

Example:

$2 = FMOV(100.5) (Signed DW)

$0 = ICNV ($2) (Signed DW)

The result is $0 = 100

„

Comparison

„

IF…THEN GOTO LABEL …

Equation: IF expression THEN GOTO LABEL identifier

If the command of expression is true, then it will go to LABEL identifier and perform the program.

Please refer to the following table for the command of expression.

Command

Description

Remark

V1 == V2

V1 is equal to V2

V1 != V2

V1 is not equal to V2

V1 > V2

V1 is greater than V2

V1 >= V2

V1 is greater than or equal to V2

V1 < V2

V1 is smaller than V2

V1<= V2

V1 is smaller than or equal to V2

V1 && V2 == 0

Perform AND command on V1 andV2 and
the result of AND operation is equal to 0

V1 && V2 != 0

Perform AND command on V1 andV2 and
the result of AND operation is not equal to 0

V1== ON

V1 is ON

V1== OFF

V1 is OFF

V1 and V2 should be internal
memory or constant.

Table 4.3.5 Comparison command table

Example:

When $2 is greater than or equal to 10, it will go to LABEL 1 and continue to perform the program.

IF $2 >= 10 THEN GOTO LABEL 1

…..

LABEL 1

…..

Equation: IFB V1 == {ON | OFF} THEN GOTO LABEL identifier

If V1 is ON or OFF, it will go to LABEL identifier to perform the program. V1 is PLC address.