Command

Equation

Descrption

SETSYSTEMTIME

SETSYSTEMTIME(V1)

Set system time

GETHISTORY

V1 = GETHISTORY (V2, V3,
V4, V5, V6)

Get history data

„

TIMETICK

TIMETICK

→ Get the time from system startup to present and put into the specific address. An

increment of 1 means 100ms is added.

„

GETLASTERROR

GETLASTERROR

→ Get last error value. If there is no error occurred, the result of GETLASTERROR

will be 0. Even if each Macro is executed simultaneously, the error message will not interfere with one

another. For error code information, please refer to section 4.4.

„

COMMENT

COMMENT

→ It lets Macro to be readable. Using this command will not affect macro function. The user

only needs to put “#” in front of the equation and the macro will become readable. If the user wants to

change the comment to be back to equation, just remove the “#” symbol.

„

Delay

Delay

→ Delays the user setting time by system. As HMI system is a multiplexer system, the system

delay problem may occur. Therefore, setting time will be increased due to “system busy” and the

condition that the setting time move forward will not happen. But too many delay time settings may

result in slow response of HMI. The unit of delay time is ms.

„

GETSYSTEMTIME

Get system time

Equation: V1 = GETSYSTEMTIME

V1 is the starting address of continuous 7 Words within the internal memory address.

V1 Year

V1 + 1 Month

V1 + 2 Date

V1 + 3 Week

V1 + 4 Hour

V1 + 5 Minute

V1 + 6 Second

Example:

Now the system time is 2006/01/04 Wed 09:26:25. Using this command to get the current system time

and store in $1~$7.