Microsens MS453490M Management Guide User Manual
Page 395

C
HAPTER
15
| Basic Administration Protocols
Remote Monitoring
– 395 –
generated, another such event will not be generated until the sampled
value has fallen below the rising threshold, reaches the falling
threshold, and again moves back up to the rising threshold.
(Range: 1-65535)
◆
Rising Event Index – The index of the event to use if an alarm is
triggered by monitored variables reaching or crossing above the rising
threshold. If there is no corresponding entry in the event control table,
then no event will be generated. (Range: 1-65535)
◆
Falling Threshold – If the current value is less than or equal to the
falling threshold, and the last sample value was greater than this
threshold, then an alarm will be generated. After a falling event has
been generated, another such event will not be generated until the
sampled value has risen above the falling threshold, reaches the rising
threshold, and again moves back down to the failing threshold.
(Range: 1-65535)
◆
Falling Event Index – The index of the event to use if an alarm is
triggered by monitored variables reaching or crossing below the falling
threshold. If there is no corresponding entry in the event control table,
then no event will be generated. (Range: 1-65535)
◆
Owner – Name of the person who created this entry. (Range: 1-127
characters)
W
EB
I
NTERFACE
To configure an RMON alarm:
1.
Click Administration, RMON.
2.
Select Configure Global from the Step list.
3.
Select Add from the Action list.
4.
Click Alarm.
5.
Enter an index number, the MIB object to be polled
(etherStatsEntry.n.n), the polling interval, the sample type, the
thresholds, and the event to trigger.
6.
Click Apply