Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 413

APS Error Messages
A–19
Display Message
Recommended Action
Description
STARTING SYMBOL MUST BE
BEFORE ENDING SYMBOL
During configuration of report options a
starting symbol that is alphabetically
after the ending symbol was entered.
Change the symbols and retry the
function.
STATION NOT GETTING SOLICITED
Valid traffic is being detected on the
network, but the software is unable to
receive the traffic.
Go to online configuration and change
the Terminal Address to a lower
address.
STS LOCAL ERROR
Unrecognized or unknown error
response from the processor.
Retry the function.
STS REMOTE ERROR
Unrecognized or unknown error
response from the processor.
Retry the function.
TERMINAL ADDRESS CANNOT
EQUAL KA5 ADDRESS
The 1785ĆKA5 and terminal are at the
same node address.
Make their node addresses unique.
TEXT EDITOR EXIT FORCED; NO
MORE ADDRESSES EXIST IN
DATABASE
While documenting a program function
key next comment" was pressed.
Retry the function.
TEXT EDITOR EXIT FORCED; NO
MORE SYMBOLS EXIST IN DATABASE
While documenting a program function
key next comment" was pressed.
Retry the function.
THIS FIELD CANNOT BE CHANGED
WHEN AUTO IS SELECTED
An attempt to change a PID value in a
field is being made while in AUTO mode.
Change the mode selection to MANUAL
by pressing [F8], Data Monitor. This can
be done offline or online.
TOO MANY INSTRUCTIONS ON A
RUNG
During program save or test edits a rung
has been detected which contains more
than 128 instructions.
Change the rung to contain no more
than 128 instructions.
UNABLE TO ACCESS USER CONFIG
DIR USING DEFAULT DIRECTORY
The specified user configuration
directory does not exist.
Use the default directory
(\ipds\attach\slc500).
UNABLE TO CONVERT ARCHIVE FILE
- CORRUPTED PROCESSOR IMAGE
The processor image is invalid.
Resave the file and retry the function.
UNABLE TO CONVERT ARCHIVE FILE
- DEVICE SIZE REQUESTED TOO
SMALL
The software cannot translate the
archive file since the processor image
will not fit into the requested PROM.
Select an alternate prom size and retry
the function.
UNABLE TO CONVERT ARCHIVE FILE
- INVALID PROCESSOR IMAGE
SAVED
The processor image is invalid.
Resave the file and retry the function.
UNABLE TO CONVERT ARCHIVE FILE
- NO PROCESSOR IMAGE
The processor image is invalid.
Resave the file and retry the function.
UNABLE TO CREATE CROSS
REFERENCE DATABASE
An attempt to update output cross
references failed.
Run CHKDSK" from the DOS command
prompt, then retry the function.
UNABLE TO CREATE PROGRAM FILE
DURING ONLINE EDITING
Program file creation is not allowed
during an online editing session.
Go offline to create program files.