Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 407

APS Error Messages
A–13
Display Message
Recommended Action
Description
INTEGRITY CHECK OF SERIAL
NUMBER HAS FAILED, REINSTALL
SOFTWARE PACKAGE
The runtime CRC does not match the
installĆtime CRC. APS aborts because
the serial number has been tampered
with.
Reinstall the software.
INVALID ADDRESS FOR SELECTED
PROCESSOR TYPE
A floating point, ASCII, or string address
exists in the ladder program.
Either change the processor type to an
SLC 5/03 Series B or SLC 5/04 or
change the ladder program to not
include these addresses.
INVALID BOARD ADDRESS
An illegal board address was entered.
Enter a valid board address and retry
the function.
INVALID GĆFILE SIZE
An attempt was made to set the GĆFile
size greater than 256 words.
Set the GĆFile size to no more than 256
words.
INVALID ISR FILE NUMBER
An attempt was made to set an ISR
number to the reserved or main ladder
program files.
Verify the destination of the ISR number.
Valid ISR numbers are 0, 4-255.
INVALID M0 FILE SIZE
An attempt was made to enter a numeric
value that can be stored as the M0 file
size.
Retry the function.
INVALID M1 FILE SIZE
An attempt was made to enter a numeric
value that can be stored as the M1 file
size.
Retry the function.
INVALID CHAR
An illegal character was entered in a file
name.
Verify that entered characters are valid.
Valid characters are: A-Z, a-z, 0-9, OR
`_'. Retry the function.
INVALID COMMAND
A key was pressed that APS was not
expecting.
Retry the function.
INVALID COMMUNICATION DRIVER
FILE FORMAT
An error occurred while trying to start the
communication driver.
Verify that the driver file exists and
execute CHKDSK" from the DOS
prompt. Retry the function.
INVALID FILE NUMBER
During program save or test edits an
error occurred while attempting to copy a
data table from the database to the
processor image.
Retry the function. If you still have
problems contact your RSI
representative.
INVALID FILE TYPE
The instruction does not permit the use
of the entered file type or the file number
is already defined as a different type of
file.
Specify a valid file type and retry the
function.
INVALID MODULE INPUT/OUTPUT
SIZE
An attempt was made to set the input or
output size greater than 32 words for a
single module.
Set the input or output size to no more
than 32 words for a single module.
INVALID OPERAND
Incorrect syntax was entered for the
operand.
Enter a valid operand and retry the