Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 268

background image

Preface

Advanced Programming Software User Manual

13–18

DH

+

Channel 1 Configuration (SLC 5/04 processors only)

When the system mode driver is DH

+

for channel 1 pressing

[F7] CH1 System

Configuration

displays the following:

Communication Driver:

DH+

Diagnostic File:

Reserved

Baud Rate:

57600

Node Address:

1 (octal)

Global Status Word Transmit Enable

0

Global Status Word Receive Enable

0

Global Status Transmit Word

S:99

Global Status Receive File

S:100–S:163

F2

UNDO

EDITS

Press a key for desired function

REM PROG

no forces

EDITS: NONE

PROC Addr 1

Channel 1 System Mode Configuration

F1

ACCEPT

EDITS

F9

CHAN

STATUS

F10

SELECT

OPTION

Global Status Word

parameters are available

only for SLC 5/04 OS401

processors.

Parameter

Description

Baud Rate

Toggles between the communication rate of 57.6K,

115.2K, and 230.4K. The default is 57.6K. A

programming terminal only can communicate on a DH+

link configured for 57.6 Kbaud. Make sure all devices

on your DH+ link are configured for the same

communication rate.

Node Address

Valid range is 0-77 octal. The default is 1.

Global Status Word Transmit Enable

Toggles between 0 and 1. The default is 0.

Global Status Word Receive Enable

Toggles between 0 and 1. The default is 0.

This parameter is only available for SLC 5/04 OS401 processors.