Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 213
Configuring Your Programming Device for Online Communication
11–19
Function Key
Description
[F1] ACK Timeout
Contains a userĆspecified value to count down the amount of
time the sender will wait per command attempt for an
acknowledgement before sending a ENQ command to the
KF3/KE. Valid multipliers are 2-65,535. The default selection
is 18.
[F2] NAK Retries
Indicates the number of times the sender is not willing to be
acknowledged by the receiver before some sort of error
recovery takes place. Valid entries are 0-255. The default
selection is 3.
[F3] ENQ Retries
Indicates the number of times the sender will request
reĆtransmission of a response from the receiver. Valid entires
are 0-255. The default selection is 3.
[F5] Command Reply Timeout
Contains a userĆspecified value multiplied by 55 ms to count
down the amount of time the sender will wait for a reply after
the command has been acknowledged. Valid multipliers are
18-25,000. The default selection is 198.
[F9] Save to File
Allows you to save the established parameters to a user
configuration file that APS accesses to automatically set up
these parameters the next time you use the software.
DF1 Full-Duplex Device Configuration (SLC 5/03 and SLC 5/04 Processors)
The SLC 5/03 and SLC 5/04 processors support DF1 full-duplex protocol via the
RS-232 connection (channel 0 for both processors) to a host computer. Refer to the
Instruction Set Reference Manual for more information on full-duplex protocol.
Note
The SLC 5/04 OS401 processor also supports bridging from DH+ to DF1
full-duplex and from DF1 full-duplex to DH+. For more information, see the
section Interchange DH+ Bridged, beginning on page 11–33.
Use a 1747-CP3 cable or a modem to connect the RS-232 channel. Refer to the SLC
500 Modular Hardware Style Installation and Operation Manual, Publication
1747-6.2 for more information on cabling.