beautypg.com

Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 213

background image

Configuring Your Programming Device for Online Communication

11–19

Function Key

Description

[F1] ACK Timeout

Contains a userĆspecified value to count down the amount of

time the sender will wait per command attempt for an

acknowledgement before sending a ENQ command to the

KF3/KE. Valid multipliers are 2-65,535. The default selection

is 18.

[F2] NAK Retries

Indicates the number of times the sender is not willing to be

acknowledged by the receiver before some sort of error

recovery takes place. Valid entries are 0-255. The default

selection is 3.

[F3] ENQ Retries

Indicates the number of times the sender will request

reĆtransmission of a response from the receiver. Valid entires

are 0-255. The default selection is 3.

[F5] Command Reply Timeout

Contains a userĆspecified value multiplied by 55 ms to count

down the amount of time the sender will wait for a reply after

the command has been acknowledged. Valid multipliers are

18-25,000. The default selection is 198.

[F9] Save to File

Allows you to save the established parameters to a user

configuration file that APS accesses to automatically set up

these parameters the next time you use the software.

DF1 Full-Duplex Device Configuration (SLC 5/03 and SLC 5/04 Processors)

The SLC 5/03 and SLC 5/04 processors support DF1 full-duplex protocol via the
RS-232 connection (channel 0 for both processors) to a host computer. Refer to the
Instruction Set Reference Manual for more information on full-duplex protocol.

Note

The SLC 5/04 OS401 processor also supports bridging from DH+ to DF1
full-duplex and from DF1 full-duplex to DH+. For more information, see the
section Interchange DH+ Bridged, beginning on page 11–33.

Use a 1747-CP3 cable or a modem to connect the RS-232 channel. Refer to the SLC
500 Modular Hardware Style Installation and Operation Manual
, Publication