Fault recovery procedure, 16œ14, Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 307: Offline config
Preface
Advanced Programming Software User Manual
16–14
Fault Recovery Procedure
To remove a fault condition and return to the RUN or REMote Run mode, do the
following:
1.
Press
CONFIG
OFFLINE
CONFIG
ONLINE
F1
, then
CONFIG
OFFLINE
CONFIG
DATA
MONITOR
F9
. Press the letter
S
and then press
[ENTER]
.
The first screen of the status file contains the fault code and fault description.
Press function key or enter value, press Alt–H for help.
S:0/0 =
offline
no forces
formatted
decimal addr
File 09TEST
F7
F5
NEXT
FILE
SPECIFY
ADDRESS
ARITHMETIC FLAGS S:0 Z:0 V:0 C:0
PROCESSOR STATUS 00000000 00000000 SUSPEND CODE 0
PROCESSOR STATUS 00000000 00000001 SUSPEND FILE 0
PROCESSOR STATUS 00000000 00000000
WATCHDOG [x10 ms] 10
MINOR FAULT 00000000 00000000 LAST SCAN [x10 ms] 0
FAULT CODE 0000 FREE RUNNING CLOCK 00000000 00000000
FAULT DESCRIPTION:
MATH REGISTER 0000 0000
ACTIVE NODE LIST I/O SLOT ENABLES
0 10 20 30 0 10 20 30
11000000 00000000 00000000 00000000 11111111 11111111 11111111 11111111
PROCESSOR BAUD RATE (Channel 1) 19200 PROCESSOR ADDRESS: 1
F9
F10
F8
CLR MIN
FAULT
CLR MAJ
FAULT
PREV
FILE
F1
PAGE
UP
F2
PAGE
DOWN
Word S:1. Bit S:1/13 in this word is the major fault bit. Cleared by
pressing
[F10] Clear Major Fault
.
Word S:5. Minor fault bits. Cleared by pressing
[F9] Clear Minor
Fault
or
[F10] Clear Major Fault
.
Word S:6. Fault code. Cleared by pressing
[F10] Clear Major
Fault
.
Fault description. A textual description of the fault code. Cleared by
pressing
[F10] Clear Major Fault
.