Configuring Your Processor for Online Communication
13–15
DF1 Full-Duplex Channel 0 Configuration
When the system mode driver is a DF1 Full-Duplex for channel 0 the following
screen is displayed:
Communication Driver:
DF1 FULL-DUPLEX
Diagnostic File:
Reserved
Baud Rate:
1200
Parity:
NONE
Stop Bits:
1
Duplicate Detect:
ENABLED
Error Detect:
CRC
ACK Timeout [20 ms]:
2
NAK Retries:
3
Source ID:
9
ENQ Retries:
3
Control Line:
NO HANDSHAKING
Embedded Responses:
ENABLED
F2
UNDO
EDITS
Press a key for desired function
REM PROG
no forces
EDITS: NONE
PROC Addr 1
Channel 0 System Mode Configuration
F1
ACCEPT
EDITS
F9
CHAN
STATUS
F10
SELECT
OPTION
You can configure the DF1 Full-Duplex driver even if the Current Communication
Mode of channel 0 is set to User.
Parameter
Description
Diagnostic File
Reserved for future use.
Baud Rate
Toggles between the communication rate of 110, 300, 600, 1200, 2400,
4800, 9600, and 19200. The default is 1200.
Parity
Toggle between None and Even. The default is None.
Stop Bits
Toggles between 1, 1.5, and 2. The default is 1.
Duplicate Packet
Detection
Toggles between Disabled and Enabled. The default is Enabled.
Error Detection
Toggles between CRC and BCC. The default is CRC.
ACK Timeout
Valid range is 2-65535 (in 20 ms increment) The default is 50.
NAK Retries
Valid range is 0-255. The default is 3.
ENQ Retries
Valid range is 0-255. The default is 3.
Control Line
Toggles between No Handshaking and FullĆDuplex modem. The default is
No Handshaking.
Embedded
Responses
Toggles between Enabled and AutoĆDetect. The default is Enabled.
Source ID
Specify the address of the sender in this field. Valid range is 0-254. The
default is 9.