Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 408
Preface
Advanced Programmming Software User Manual
A–14
Display Message
Recommended Action
Description
KF3 ADDRESS CANNOT EQUAL
PROCESSOR ADDRESS
The 1770ĆKF3 and processor are at the
same node address.
Change their node addresses to be
unique.
LINK ERROR
Unrecognized or unknown problem with
the communication driver.
Retry the function. If you still have
problems contact your RSI
representative.
LOSS OF MODEM CARRIER
While online with DF1 Full Duplex
through a 1770ĆKF3 and a modem, a
disconnection or hangup occurred.
Retry the function.
LOSS OF MODEM DSR STATUS
While online with DF1 Full Duplex
through a 1770ĆKF3, the modem went
inactive.
Check the connection and retry the
function.
M0/M1 ADDRESS MONITORING ONLY
SUPPORTED ONLINE
An attempt to monitor an M0/M1 file was
made using a processor other than an
SLC 5/03.
Change the processor to an SLC 5/03;
go online with APS; retry M0/M1 address
monitoring.
M0/M1 ADDRESS MONITORING
CURRENTLY DISABLED
M0/M1 address monitoring is disabled in
the APS configuration.
Enable M0/M1 address monitoring and
retry the function.
M0/M1 ADDRESSES CANNOT BE
MODIFIED
Unable to modify M0/M1 addresses from
the M0/M1 data table monitor.
Informational message. You cannot
modify M0 and M1 files from the data
table monitor.
MAXIMUM COMMUNICATION DRIVER
SIZE EXCEEDED
The link layer driver is too large to fit into
the memory available.
Verify the size, date, and time for the link
layer file. Also run CHKDSK" from the
DOS prompt.
MAXIMUM NODE ADDRESS
VIOLATION DETECTED
The software detected a device at a
node higher than the current maximum
node address.
Change the Max. Node Address in the
online Configuration screen.
MESSAGE TIMEOUTS - LOSS OF
COMMUNICATIONS
Either 1) the specified device is currently
busy; 2) the requested device is not at
the specified address; 3) the requested
device is not at the specified baud rate;
4) the PC may not be able to
communicate through the requested port
at the selected baud rate; or 5) electrical
noise exists in the network wiring.
1) Verify all addresses and baud rates;
2) verify that the SLC has power and
that it is sufficient to run the processor;
3) check the power supply jumper on the
processor, verify positioning for the
current input power; 4) use the Who
function to determine network
configuration; or 5) correct noise
problem.
MODULE MUST BE SPECIFIED
BEFORE SPECIAL CONFIG.
The Special I/O function key was
pressed while the highlighted slot was
empty.
Specify module and retry function.
MULTIPOINT ADDRESSES MUST
ALREADY EXIST
An attempt to add an address to the
multiĆpoint list was made, but failed
since the address does not currently
exist in the program.
Specify the address in the program and
then retry the function.