Preface, Offline config, Accepting a rung – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 335

Preface
Advanced Programming Software User Manual
17–14
[F10] Cancel Edits
If you want to discard your modifications made during online editing, press
CONFIG
OFFLINE
CONFIG
CANCEL
EDITS
F10
. This prevents them from being assembled into your ladder program.
Canceling edits can only be done if edits are not currently being tested.
•
Canceling edits removes the online editing changes from the program and
removes the edit zones.
•
When edits are canceled, all replace and delete edit zone markers are removed
and all rungs marked with insert edit zone markers are deleted from the ladder
program.
Note
Canceling edits does not restore data table values that were altered during an online
editing session.
When performing this function your scan time and interrupt latency can increase by
10 ms per scan.
Accepting a Rung
Edits are sent to the processor when you accept a rung. Once you accept the rung,
the data values are applied and the message:
DATA TABLE VALUES HAVE
BEEN PERMANENTLY MODIFIED
is displayed.
On accepting a rung, the scan time and interrupt latency may increase up to
10 ms per scan. Note that although data table values have changed
permanently, the rung changes are not permanent. You must test and then
assemble your edits to make your edits permanent.
Note
Be careful of the types of ladder programs you choose to edit online. Programs that
have future access (OEM Lock) set to “disallow” must be saved to disk prior to
exiting APS. Failure to do this will prohibit you from accessing the program in the
future.