Preface, Offline config – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 256

Preface
Advanced Programming Software User Manual
13–6
2.
Access the Channel Configuration display by pressing
CONFIG
OFFLINE
CONFIG
CHANNEL
CONFIG
F5
. The
following display shows the default parameters for an SLC 5/03 OS301, OS302
processor.
CHANNEL 0 CONFIGURATION
Current Communication Mode:
SYSTEM
System Mode Driver:
DF1 FULL-DUPLEX
User Mode Driver:
GENERIC ASCII
Write Protect:
DISABLED
Mode Changes:
DISABLED
Mode Attention Character:
/1b
System Mode Character:
S
User Mode Character:
U
Edit Resource/File Owner Timeout:
60 (seconds)
Passthru Link ID:
1 (decimal)
CHANNEL 1 CONFIGURATION
System Mode Driver:
DH-485 MASTER
Write Protect:
DISABLED
Edit Resource/File Owner Timeout:
60 (seconds)
Passthru Link ID:
2 (decimal)
F2
UNDO
EDITS
Press a key for desired function
REM PROG
no forces
EDITS: NONE
PROC Addr 1
Channel Configuration
F1
ACCEPT
EDITS
F4
CH0 SYS
CONFIG
F7
CH1 SYS
CONFIG
F10
SELECT
OPTION
F5
CH0 USR
CONFIG
Available Function Keys
Description
[F1] Accept Edits
Accepts all changes made to the general channel
configuration.
[F2] Undo Edits
Discards any changes made to the general channel
configuration since the last time the Accept Edits key was
pressed.
[F4] Channel 0 System
Configuration
Accesses the channel 0 configuration screen for the selected
system mode communication driver.
[F5] Channel 0 User
Configuration
Accesses the channel 0 configuration screen for the selected
user mode communication driver. This option only applies to
SLC 5/03 OS301, OS302 and SLC 5/04 OS400, OS401
processors.
[F7] Channel 1 System
Configuration
Accesses the channel 1 configuration screen for the selected
system mode communication driver.
[F10] Select Option
Changes the value for the currently cursored option.
3.
Leave the channel configuration screen by either accepting the edit or undoing
the edit.