Parameter
Description
Diagnostic File
Reserved for future use.
Baud Rate
Toggles between the communication rate of 110, 300, 600, 1200,
2400, 4800, 9600, and 19200.
Parity
Toggles between None and Even. The default is None.
Stop Bits
Toggles between 1, 1.5, and 2. The default is 1.
Station Address
The valid range is 0-254 decimal. The default is 1.
Duplicate Packet Detection
Toggles between Enabled and Disabled. The default is Enabled.
Error Detection
Toggles between CRC and BCC. The default is CRC.
ACK Timeout
Allows you to select the ACK timeout value in increments of 20 ms.
The valid range is 0-65535.
RTS Off Delay
Allows you to select the RTS off delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
Message Retries
Allows you to select the message retries value. The valid range is
0-255. The default is 3.
RTS Send Delay
Allows you to select the RTS send delay value in increments of
20 ms. The valid range is 0-65535. The default is 0.
PreĆsend Time Delay
Allows you to select the RTS preĆtransmit time delay in increments
of 20 ms. The valid range is 0-65535.
Control Line
Toggles between No Handshaking, FullĆDuplex Modem, and
HalfĆDuplex Without Continuous Carrier.
Polling Mode
Toggles between Message Based (Do Not Allow Slave to Initiate
Messages), Message Based (Allow Slave to Initiate Messages),
Standard (Single Message Transfer Per Node Scan), and Standard
(Multiple Message Transfer Per Node Scan).
Priority Polling - Low
Allows you to select the Priority Polling Range Low Address. The
valid range is 0-255.
Normal Polling - Low
Allows you to select the Normal Polling Range Low Address. The
valid range is 0-255.
Priority Polling - High
Allows you to select the Priority Polling Range High Address. The
valid range is 0-254.
Normal Polling - High
Allows you to select the Normal Polling Range High Address. The
valid range is 0-254.
Reply Message Wait Time
Allows you to select the Reply Message Wait Time setting in
increments of 20 ms. The valid range is 0-65535.
Normal Poll Group Size
Allows you to select the Normal Poll Group Size. The valid range
is 0-255.