Df1 half-duplex slave device configuration – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 217

Configuring Your Programming Device for Online Communication
11–23
DF1 Half-Duplex Slave Device Configuration
The SLC 5/03 and SLC 5/04 processors support half-duplex protocol via RS-232
(channel 0 for both processors). In contrast to DF1 full-duplex, DF1 half-duplex
communication takes place in only one direction at a time. Refer to the Instruction
Set Reference Manual for more information on Half-Duplex DF1 Slave protocol.
Note
It is not possible for APS and an SLC 5/03 or SLC 5/04 processor to communicate
using DF1 half-duplex protocol unless one of the processors or another device is
configured to be a DF1 half-duplex master.
F1
Port
COM1
Current Device
Half-Duplex Slave
F4
Terminal Address
0
F5
PROC Address
1
F7
Device/Modem/Half-Duplex Configuration
F9
Save to File
F9
Press a function key
SAVE TO
FILE
F5
PROC
ADDRESS
F1
PORT
F2
SELECT
DEVICE
F4
TERM
ADDRESS
ESC exits/Alt-U aborts changes
ONLINE CONFIGURATION
F7
DEVICE
CONFIG
Function Key
Description
[F1] Port
Toggles between COM1 and COM2. This field indicates
where the processor is connected to your computer. The
default is COM1.
[F2] Select Device
Toggles between the selected interface card and the interface
card selection menu.
[F4] Terminal Address
Allows selection of a terminal address as a node number.
Valid range is 0–254 decimal. The default is 0.
[F5] Processor Address
Allows selection of a processor address as a node number.
Valid range is 1–254 decimal. The default selection is 1.
[F7] Device Configuration
Allows you to select the configuration parameters for the
specified device.