Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 410

Preface
Advanced Programmming Software User Manual
A–16
Display Message
Recommended Action
Description
NOT A LADDER FILE
An attempt to jump to a ladder file was
made, but the file number specified is
not a ladder file.
Verify the operation and specify a valid
ladder file.
NOT ENOUGH MEMORY FOR
COMMUNICATION DRIVER
The software package tried to load files
that exceeded 128KBytes.
Retry the function and if necessary exit
and restart the software. If the error
continues validate the disk by running
the CHKDSK" from the DOS prompt.
ONLINE EDITING NOT AVAILABLE,
INVALID KEYSWITCH POSITION
Online editing is not allowed when the
SLC 5/03 or SLC 5/04 keyswitch is in the
Run position.
Change the keyswitch to the Remote or
Program position. Retry the function.
OPERAND MUST BE INDEXED
The operand for the current instruction is
not indexed.
Index the operand and retry the function.
OPERATOR ABORTED DIALUP
While going online with DF1 Full Duplex
through a 1770ĆKF3 and a modem the
[ESC] key was pressed.
Retry the function.
OUT OF DATA TABLE MEMORY
During program save or test edits an
error occurred while attempting to copy a
data table from the database to the
processor image.
The program is too large. Reduce the
program memory requirements.
OUT OF MEMORY IN PROCESSOR
IMAGE
Either 1) during program save or test
edits all available memory in the
processor image was used by the
program; or 2) the program is too big for
the processor.
The program is too large. Reduce the
program memory requirements.
OUT OF MEMORY IN PROGRAMMING
DEVICE
During program save or test edits all
available memory in the programming
device was used.
The program is too large. Reduce the
program memory requirements.
PARSE ERROR
Entry on line was an invalid file or rung
number.
Verify file or rung entry and retry the
function.
PLINK Errors
These errors indicate software package
problems.
Attempt to reinstall APS and call your
RSI representative.
POINT IS PROTECTED, FUNCTION
NOT AVAILABLE
An attempt to change the state of a
protected bit was made, either from the
online multiĆpoint list, or from a force
menu.
Informational message. No action
necessary.
PROBLEMS ENCOUNTERED DURING
ASSEMBLE/CANCEL EDITS
A problem exists with the database
assemble/cancel edits function.
Contact your local RSI representative.
PROCESSOR DATA VALUES MAY
HAVE CHANGED
During quick edits, when switching from
offline to online monitoring, the offline
data tables were downloaded.
Changes to the processor data tables
may occur if the offline data tables do
not match the online data tables. Verify
for the correct data tables.