IAI America SCON-CA User Manual
Page 84
Chapter 2 Wiring
74
[4] Pulse converter : JM-08
The pulse converter converts feedback pulses in the differential mode into those in the open
collector mode.
Use this converter in the case the pulse input of the host controller is open collector (24V)
type.
Host Controller
(PLC etc.)
SCON-CA
Caution
1) Pay attention not to insert wrongly because it is the same e-CON connector as
input and output. Putting the power on with the insertion being wrong will burn
JM-08.
2) Use the pulse converter in the ambient temperature range between 0ºC and 40ºC.
3) The temperature increase of about 30ºC occurs during operation. Accordingly,
neither install several pulse converters in close contact nor install them within a
duct. Do not install the pulse converter near other heating devices.
4) If more than one pulse converters are installed, set a pulse converter apart from another
by 10mm or more.
5) Make the wiring between the host controller (PLC, etc.) and JM-08 as short as possible.
Long one is easy to pick the noise. Also make the wiring between JM-08 to SCON-CA
as short as possible.
Place JM-08 close to the host controller.
A recommended installation sample is shown in the figure below.
•
Make the cable length between the host controller and pulse converter as short as possible.
Wiring length :
50mm or shorter recommended
Host Controller
•
Keep pulse converters separated for 10mm or more from each other.
10mm or more
10mm or more
If this installation cannot be
avoided, shorten the length of
the wiring with the host
controller as much as possible.