IAI America SCON-CA User Manual

Page 157

background image

Chapter 3 Operation

147

[1]

Initial

Setting

Pressing by pressing operation using force sensor uses a loadcell. Before the operation can be

started, parameters must be initialized. Set the four parameters listed in the table below as

shown in the area enclosed by the thick frame.

No.

Name

Set value for

actuator with

loadcell

Set value for

pressing

operation

using force

sensor

Reference

92

Use of loadcell

[0: No use / 1: Use]

1

1

0: No use of loadcell

1: Use of loadcell

93

Selection of pressing control

[0: Current limit / 1: Force

sensor]

1

1

0: Control by current limit (normal

control)

1: Control by force sensor

117

Automatic loadcell calibration

at start

[0: Yes / 1: No]

1

1

(Recommended)

or

0

0: No automatic calibration of

loadcell

1: Automatic calibration of

loadcell

118

Pressing operation without

completion of loadcell

calibration

[0: Disable / 1: Enable]

0

0

0: Pressing disabled in no

completion of calibration

1: Pressing enabled in no

completion of calibration

(1) Set of pressing control by loadcell

1) Set Parameter No.92 “Use of loadcell” to “1” “use”. If Parameter No.92 is set to “0” (Does

not use), the loadcell is invalid.

2) Set Parameter No.93 “Selection of pressing control” to “1” “pressing by pressing operation

using force sensor”. If Parameter No.93 is set to “0”, pressing by current limit is selected.

[Settings of Parameter No.92 and 93 and pressing control]

Parameter No.92

Use of loadcell

Parameter No.93

Selection of pressing control

Pressing control

1: Control by force sensor

Pressing by pressing

operation using force sensor

1: Use of loadcell

0: Control by current limit

Pressing by current limit

1: Control by force sensor

Alarm 0A1

Parameter data error

0: No use of loadcell

0: Control by current limit

Pressing by current limit

(2) Set of calibration of loadcell

Perform the settings to set when to have the calibration and to protect from the operation

without the calibration.

1) To measure precise force, proper loadcell calibration is required. Set Parameter No.117

“Automatic calibration at start” to “1” to perform calibration automatically or “0” to perform

calibration arbitrarily.

If it is set to automatic setting, the calibration is conducted once after the power is supplied

to the controller or software reset is held from the teaching tool such as PC software. The

calibration time is 10ms. The calibration does not lead the actuator to be operated.

2) Parameter No.118 can provide protection so that pressing may not be performed without

calibration. Set the parameter to “0”. Pressing without any calibration after power-on

causes alarm 0E1 “calibration error” to occur.

Setting the parameter to “1” allows pressing without calibration to be performed.