Chapter 8 I/O Parameter

229

[109] Home preset value (Parameter No.139)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

139 Home preset value

PRST

mm

-9999.99 to

9999.99

In accordance

with actuator

For the actuator of absolute specification, set this parameter so that (home return offset + value

of this parameter) is within the range between 0 and the ball screw lead.

The value should be an integer multiple of ±(ball screw lead length) including 0.00.

(If the home return offset is within the range between 0 and ball screw lead length, the value of

this parameter is 0.00.)

When this parameter is set to a value other than 0.00, the home return complete position is

determined by calculating (home position + position set by this parameter)

For the actuator of incremental specification, always set this parameter to 0.00.

With ball screw lead length 4mm and home return offset level 10mm, set this parameter to

-8mm.

Caution: If the above condition is not satisfied, the home position at restart after home

return may shift by an integer multiple of the ball screw lead.

Home Return Offset Level (10mm)

Home position preset value (-8mm)

Home return

completion position

[-8mm]

Ball Screw Lead Length (4mm)

Ball Screw Lead Length (4mm) Ball Screw Lead Length (4mm)

Home Position

[0mm]