Chapter 6 Power-saving Function (Auto Servo-motor OFF Function)
184
(3) Status of positioning complete signal in selection of automatic servo OFF
Automatic servo OFF causes the actuator to be in other than the positioning complete state
due to the servo OFF. Positioning complete signal (PEND) is turned OFF. Changing the
PEND signal to the in-position signal judging whether the actuator is stopped within the
positioning width zone instead of the positioning complete signal allows PEND not to be
turned OFF during servo OFF.
This setting is reflected on complete position numbers PM1 to PM** in PIO patterns 0 to 3
and 6 confirming the positioning complete position No. or current position numbers PE* in
PIO patterns 4 and 7.
Define the setting in Parameter No.39.
Signal outputs during automatic servo OFF
Value set in
Parameter No.39
Content of PEND signal
PEND
PM1 to M**
PE**
0
Positioning Completion Signal
OFF
OFF
OFF
1
In-position Signal
ON
ON
ON
(Note) The SV on the front panel blinks green during the automatic servo OFF.
[For Parameter No.39 = 0]
Operation of actuator
Positioning
operation
Automatic servo OFF
standby
Servo OFF
Positioning
operation
Servo Condition
ON
ON
OFF
ON
Completed Position No.
Input (Current position
number output)
PM1 to ** =0
(PE** = OFF)
PM1 to ** = Output
(PE** = ON)
PM1 to ** = 0
(PE** = OFF)
PM1 to ** = 0
(PE** = OFF)
Positioning Completion
Signal PEND
OFF
ON
OFF
OFF
Servo OFF Delay
Time
(Parameter No.36 to 37)
[For Parameter No.39 = 1]
Operation of actuator
Positioning
operation
Automatic servo OFF
standby
Servo OFF
Positioning
operation
Servo Condition
ON
ON
OFF
ON
Completed Position No.
Input (Current position
number output)
PM1 to ** = 0
(PE** = OFF)
PM1 to ** = Output
(PE** = ON)
PM1 to ** = 0
Output
(PE** = ON)
PM1 to ** = 0
(PE** = OFF)
Positioning Completion
Signal PEND
OFF
ON
ON
OFF
Servo OFF Delay
Time
(Parameter No.36 to 37)