Chapter 3 Operation

152

3.3.2 Operation Ready and Auxiliary Signals

[1] System Ready (PWR)

Output

PIO signal

PWR

The signal is turned ON if the controller can be controlled after main power-on.

It is turned ON once the initialization terminates normally after main power-on and SCON can

be controlled regardless of alarm and servo status.

Even in the alarm condition, when the SCON can control the system, it is turned “ON”.

The signal is synchronized with the illumination of the PWR LED (GN) on the front face of the

controller.

[2] Emergency stop status (*EMGS)

Output

PIO signal

*EMGS

1) Emergency Stop Status EMGS is usually turned on and is turned off when “2.2.3 [3] Power

and Emergency Stop Circuit” is open between EMG+ and EMG- (emergency stop condition

or not connected).

2) It turns back on if the emergency stop condition is cancelled and the circuit is closed

between EMG+ and EMG-. Have an appropriate safety treatment such as interlock with this

signal for the host controller (PLC, etc.).

� �

Caution: It is not an emergency stop output due to an alarm generation of the

controller.