Chapter 8 I/O Parameter

206

[20] PIO pattern selection (Parameter No.25)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

25 PIO pattern selection

IOPN

0 to 7

0 (Standard Type)

Select the PIO operation pattern in Parameter No.25.

Check the 3.2 Operation in Positioner Mode for details of PIO patterns.

Pattern type

Value set in

Parameter

No.25

Mode

Feature of PIO pattern

PIO

pattern 0

0

(factory

setting)

Positioning mode

(Standard type)

Number of positioning points: 64

Position command: Binary code

Zone signal output: 1 point

Position zone signal output: 1 point

PIO

pattern 1

1

Teaching mode

(Teaching type)

Number of positioning points: 64

Position command: Binary code

Position zone signal output: 1 point

Jog operation enabled by PIO signal

Writing current position data to position table

enabled by PIO signal

PIO

pattern 2

2

256-point mode

(256-point type)

Number of positioning points: 256

Position command: Binary code

Position zone signal output: 1 point

PIO

pattern 3

3

512-point mode

(512-point type)

Number of positioning points: 512

Position command: Binary code

Zone signal output: None

PIO

pattern 4

4

Solenoid valve

mode 1

(7-point type)

Number of positioning points: 7

Position command: Individual No. signal ON

Zone signal output: 1 point

Position zone signal output: 1 point

PIO

pattern 5

5

Solenoid valve

mode 2

(3-point type)

Number of positioning points: 3

Position command: Individual No. signal ON

Signal equivalent to LS (limit switch) enabled

Zone signal output: 1 point

Position zone signal output: 1 point

PIO

pattern 6

6

Pressing

Operation Using

Force Sensor

Mode 1

Number of positioning points: 32

Position command: Binary code

Position zone signal output: 1 point

Judgment of pressing force enabled

PIO

pattern 7

7

Pressing

Operation Using

Force Sensor

Mode 2

(Solenoid valve

Type)

Number of positioning points: 5

Position command: Individual No. signal ON

Position zone signal output: 1 point

Judgment of pressing force enabled