Chapter 8 I/O Parameter

218

[61] Electromagnetic brake power monitor (Parameter No.75)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

75 Electromagnetic brake power

monitor

FSTP

0: Disabled

1: Enabled

In accordance with

actuator

A power monitor function is provided to prevent actuator malfunction or breakdown of parts

caused by an abnormal voltage of the 24V DC brake power supply when an actuator with brake

is used.

Normally this parameter need not be changed because it has been set properly prior to the

shipment in accordance with the actuator, i.e. whether or not the actuator is equipped with

brake.

Set Value

Description

0

Disabled (no brake)

1

Enabled (with brake)

[62] Belt breaking sensor input polarity (Parameter No.76)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

76 Belt breaking sensor input

polarity

AIOF

0 to 2

In accordance with

actuator

Set the sensor input polarity for Alarm Code 0D7 “Belt Break Detection” for Ultra-High Thrust

Type RCS2-RA13R.

Parameter No.

Set Value

not used

0

Input is a contact

1

76

Input is b contact

2

[63] Ball Screw Lead Length (Parameter No.77)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

77 Ball Screw Lead Length

LEAD

mm

0.01 to 999.99

In accordance with

actuator

This parameter set the ball screw lead length.

The factory setting is the value in accordance with the actuator characteristics.

Caution: If this parameter is set to “Disabled”, no brake control is provided.

Caution: Changing the setting of this parameter disables the alarm to be detected.

Caution: If the setting is changed, not only the normal operation with indicated speed,

acceleration or amount to move is disabled, but also it may cause a

generation of alarm, or malfunction of the unit.