Overload level ratio (parameter no. 143) – IAI America SCON-CA User Manual
Page 240
Chapter 8 I/O Parameter
230
[110] IP Address (Parameter No.140)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
140
IP Address
IPAD
–
0.0.0.0 to
255.255.255.255
192.168.0.1
It is the parameter dedicated for Fieldbus (EtherNet/IP).
[For details, refer to Fieldbus Instruction Manual.]
[111] Subnet Mask (Parameter No.141)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
141
Subnet Mask
SNMK
–
0.0.0.0 to
255.255.255.255
255.255.255.0
It is the parameter dedicated for Fieldbus (EtherNet/IP).
[For details, refer to Fieldbus Instruction Manual.]
[112] Default Gateway (Parameter No.142)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
142
Default Gateway
DFGW
–
0.0.0.0 to
255.255.255.255
0.0.0.0
It is the parameter dedicated for Fieldbus (EtherNet/IP).
[For details, refer to Fieldbus Instruction Manual.]
[113]
Overload Level Ratio (Parameter No. 143)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
143
Overload Level Ratio
OLWL
%
50 to 100
100
With the motor temperature of when an operation is held at the rating being set as 100%, the
overload warning (message level) is output when the motor temperature exceeds the rate set in
this parameter.
The judgment would not be made if the value is set to 100%.
[114] Total Movement Count Threshold�(Parameter No.147)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
147
Total Movement Count
Threshold
TMCT
Times
0 to 999999999
0(Disabled)
An alarm is generated when the total movement count exceeds the value set to this parameter.
The judgment would not be made if the value is set to 0.
[115] Total Operated Distance Threshold (Parameter No.148)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
148
Total Operated Distance
Threshold
ODOT
m
0 to 999999999
0(Disabled)
An alarm is generated when the total operation distance exceeds the value set to this
parameter.
The judgment would not be made if the value is set to 0.