IAI America SCON-CA User Manual
Page 258
Chapter 9
Troubleshooting
248
Alarm
Code
Alarm
Level
Alarm Name
Cause/Treatment
0A1
Cold start
Parameter data error
Cause
: The data input range in the parameter area is not
appropriate.
This error occurs when the magnitude relationship
is apparently inappropriate such as when 300mm
was incorrectly input as the value of the soft limit
negative side while the value of the soft limit
positive side was 200.3mm.
Treatment : Change the value to the appropriate one.
0A2
Position data error
Cause
: 1) A move command was input when no target
position was set in the “Position” field of a
position No. in the position table.
2) The value of the target value in the “Position”
field exceeded the Parameter No.3 and 4 “Soft
limit set value”.
3) A target position was specified in the “Position”
field by relative coordinate in the solenoid valve
mode 2 of PIO pattern 5.
4) Pressing operation was specified while the
vibration suppress control function remained
effective.
Treatment : 1) Set the target position.
2) Change the target position value to the one
within the soft limit set value.
3) The target position cannot be set by relative
coordinate (incremental feed).
4) The vibration suppress control function and
pressing operation cannot be used concurrently.
Provide setting so that either of the functions is
effective.
0A3
Position command data
error
Cause
: 1) The speed or acceleration/deceleration value
during direct numeric specification exceeded the
maximum set value.
2) Pressing operation was specified in the field bus
specification while the vibration suppress
function remained effective.
Treatment : 1) Table to input a proper value.
2) The vibration suppress control function and
pressing operation cannot be used concurrently.
Provide setting so that either of the functions is
effective.
0A4
Command counter
overflow
Cause
: The number of input command pulses exceeded
the range of -134217728 to +134217728
(H'F8000000 to '07FFFFFF).
Treatment : Attempt to make the value of the electrical gear
ratio smaller (make the movement against the unit
bigger).
0A5
Operation
release
Electromagnetic brake
unreleased error
Cause
: The brake cannot be released.
Treatment : Supplied the 24V power unit for the electromagnetic
brake.
0A6
Cold start
Dynamic brake not
released
Cause
: The dynamic brake cannot be released when the
servo is ON due to noise and electrostatic, etc.
Treatment : Implement measures to eliminate noise or
electrostatic.
There is a concern of circuit breakdown. Please
contact IAI.