Functions – Pilz PSS SB HYD, Basic license User Manual

Page 97

background image

Modular Block System: Hydraulic Presses

6-35

Functions

The operation of SB064 is established via the following input parameters:

ARSt:

No reset lock (Automatic Restart)

AuSt:

No start-up disabler (Automatic Start) on PSS cold/warm start
or when starting the I/O-Group

NoFT:

No function test on the gate

Please note that a combination of various settings is possible with these
input parameters (e.g. start-up disabler activated/reset lock activated or
start-up disabler activated/reset lock disabled etc.). These input
parameters are also used to establish what the operator needs to do
should an error occur (function test and error acknowledgement/reset).
The individual options can be found in the following tables.

Tables for setting the functions:

Procedure for achieving the enable (output parameter

ENBL) on PSS cold/

warm start

Op. mode

Start disabler

AuSt

0

0

0

1

*1

0

1

*1

Parameter

ARSt

0

1

0

0

1

1

NoFT

0

0

1

1

1

1

Func- Status of gate

open shut open shut open shut open shut open shut open shut

tion

Close gate

x

*2

-

x

*2

-

x

-

x

-

x

-

x

-

test Open and close

x

*2

x

x

*2

x

-

-

-

-

-

x

*3

-

-

gate

or

RSET

-

-

-

-

Table 1: Function: “Start-up disabler”