Modular Block System: Hydraulic Presses

Standard Function Blocks

• Error messages in DB015

- Bit 00:

N/O contacts 1 and 2 on ESPE/AOPD (input parameter

NO_1

and

NO_2) are not synchronised

Remedy: Check inputs, cable, input card and all conditions,
reset and then carry out a function test.

- Bit 02:

Time exceeded on test of ESPE/AOPD
Remedy: Check inputs, cable, input card and all conditions,
reset and then carry out a function test.

- Bit 05:

Start-up disabler; not yet reset
Remedy: Reset (input parameter

RSET)

- Bit 07:

Change of operating mode
Remedy: Reset reset lock

- Bit 08:

Protected field broken
Remedy: Clear protected field, reset if necessary.
Otherwise: Check inputs, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 09:

Start-up disabler
Remedy: Carry out a function test on the ESPE/AOPD and
reset (input parameter

RSET)

- Bit 10:

Cycle start-up disabled, manual start (initial start with cycle
mode)
Remedy: Depends on which cycle mode is selected (input
parameter

STyp):

STyp = 0: Break the protected field, clear it and then press the

reset button (input parameter

RSET).

STyp = 1: Press the reset button (input parameter RSET),

break the protected field and then clear it.

- Bit 11:

Cycle lock active, waiting for pulse 1
Remedy: Break protected field and re-enable

- Bit 12:

Cycle lock active, waiting for pulse 2
Remedy: Break protected field and re-enable

- Bit 13:

Cycle disable time exceeded, manual start (initial start with
cycle mode)
Remedy: Depends on which cycle mode is selected:

SB068