Modular Block System: Hydraulic Presses
Standard Function Blocks
• Error messages in DB015
- Bit 00:
N/O contacts 1 and 2 on ESPE/AOPD (input parameter
NO_1
and
NO_2) are not synchronised
Remedy: Check inputs, cable, input card and all conditions,
reset and then carry out a function test.
- Bit 02:
Time exceeded on test of ESPE/AOPD
Remedy: Check inputs, cable, input card and all conditions,
reset and then carry out a function test.
- Bit 05:
Start-up disabler; not yet reset
Remedy: Reset (input parameter
RSET)
- Bit 07:
Change of operating mode
Remedy: Reset reset lock
- Bit 08:
Protected field broken
Remedy: Clear protected field, reset if necessary.
Otherwise: Check inputs, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 09:
Start-up disabler
Remedy: Carry out a function test on the ESPE/AOPD and
reset (input parameter
RSET)
- Bit 10:
Cycle start-up disabled, manual start (initial start with cycle
mode)
Remedy: Depends on which cycle mode is selected (input
parameter
STyp):
STyp = 0: Break the protected field, clear it and then press the
reset button (input parameter
RSET).
STyp = 1: Press the reset button (input parameter RSET),
break the protected field and then clear it.
- Bit 11:
Cycle lock active, waiting for pulse 1
Remedy: Break protected field and re-enable
- Bit 12:
Cycle lock active, waiting for pulse 2
Remedy: Break protected field and re-enable
- Bit 13:
Cycle disable time exceeded, manual start (initial start with
cycle mode)
Remedy: Depends on which cycle mode is selected:
SB068
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license