Sb052: operating mode selector switch, 2 from 6, Block header, Input parameters – Pilz PSS SB HYD, Basic license User Manual
Page 72: Standard function blocks, Sb052

6-10
Modular Block System: Hydraulic Presses
Standard Function Blocks
SB052: Operating mode selector switch, 2 from 6
Block header
Input parameters
•
SSNR:
Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB 001 ... KB 200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
•
S1 ... S6: Switch levels from coded operating mode selector switch
On each position of the selector switch, a 1-signal must be
present at two switch contacts only.
If a maximum of 6 switch settings (operating modes) are used,
switch contacts S5 and S6 may be omitted (see table overleaf:
“Input coding of selector switch”).
If a maximum of 10 switch settings are used, switch contact S6
may be omitted (see table overleaf: “Input coding of selector
switch”).
Unused inputs should be assigned RLO-0 (M 110.00).
SB052
BA_2AUS6
B - SSNR
X - S1
X - S2
X - S3
X - S4
X - S5
X - S6
X - RSet
X - LOCK
W- TIME
FG
- X
BA
- W
RSET - X
SB052
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license