6-144
Modular Block System: Hydraulic Presses
Standard Function Blocks
Error messages
Any fault that is detected will be stored in the corresponding error data
word (
SSNR) of DB015 (1st data block), until the fault has been fully dealt
with.
• Error messages in DB015
- Bit 00:
Invalid operation of input parameter
Y1On or Y2On
Remedy: See section entitled “Function”. Once the error has
been rectified, reset (input parameter
RSET)
- Bit 01:
Valve acknowledgement input parameter
S1 remains high after
the valve is switched on
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 02:
Valve acknowledgement input parameter
S1 remains low after
the valve is switched off
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
INFORMATION
If no reaction time has been set for switching off the valve
(
TOff = 0), Bit 02 will remain set until the valve returns to its
start position. This is not a fault, but is important to bear in
mind.
- Bit 03:
Valve acknowledgement input parameter
S1 goes to its start
position during operation (input parameter
S1 goes high while
output parameter
Y1 = 1)
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 04:
Valve Y1 not in its start position (off) when switched on, i.e.
signal at input parameter
S1 • 1
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
SB088
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license