Output parameters, Standard function blocks, Sb075 – Pilz PSS SB HYD, Basic license User Manual
Page 172

6-110
Modular Block System: Hydraulic Presses
Standard Function Blocks
Input circuitry
Connect the input parameters S1, S2 and LCKD as follows:
If you are using 2 gate switches and a guard locking monitoring circuit:
• Assign the relevant input parameters as specified in the section entitled
“Input parameters”.
If you are using one gate switch and one combined gate switch/guard
locking monitoring circuit:
• Assign the input parameters S1 and S2 to the signal from the gate switch
(both input parameters to the same signal).
• Assign the input parameter LCKD to the signal from the combined gate
switch/guard locking monitoring circuit:
Input parameter S1
: Gate switch
Input parameter S2
: Gate switch
Input parameter LCKD
: Gate switch/guard locking monitoring circuit
WARNING!
The gate switch signal and the signal from the combined gate switch/guard
locking monitoring circuit must not be connected in series.
Output parameters
•
ENBL:
Enable flag bit
ENBL = 0 : Error detected (e.g. gate opened)
ENBL = 1 : The enable is given if the gate is closed and
locked and no error has been detected
•
UNLK:
Controlling the guard locking (electromagnet)
UNLK = 0 : Lock gate
UNLK = 1 : Unlock gate
WARNING!
The guard locking device must operate to normally energised
mode, i.e. the gate must be unlocked when operating voltage
is applied (
UNLK = 1)!
Use of a guard locking device that operates to normally de-
SB075
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license