6-110

Modular Block System: Hydraulic Presses

Standard Function Blocks

Input circuitry

Connect the input parameters S1, S2 and LCKD as follows:

If you are using 2 gate switches and a guard locking monitoring circuit:

• Assign the relevant input parameters as specified in the section entitled

“Input parameters”.

If you are using one gate switch and one combined gate switch/guard
locking monitoring circuit:

• Assign the input parameters S1 and S2 to the signal from the gate switch

(both input parameters to the same signal).

• Assign the input parameter LCKD to the signal from the combined gate

switch/guard locking monitoring circuit:

Input parameter S1

: Gate switch

Input parameter S2

: Gate switch

Input parameter LCKD

: Gate switch/guard locking monitoring circuit

WARNING!

The gate switch signal and the signal from the combined gate switch/guard
locking monitoring circuit must not be connected in series.

Output parameters

ENBL:

Enable flag bit
ENBL = 0 : Error detected (e.g. gate opened)
ENBL = 1 : The enable is given if the gate is closed and

locked and no error has been detected

UNLK:

Controlling the guard locking (electromagnet)
UNLK = 0 : Lock gate
UNLK = 1 : Unlock gate

WARNING!

The guard locking device must operate to normally energised
mode, i.e. the gate must be unlocked when operating voltage
is applied (

UNLK = 1)!

Use of a guard locking device that operates to normally de-

SB075