Standard function blocks, Sb089 – Pilz PSS SB HYD, Basic license User Manual

Page 218

background image

6-156

Modular Block System: Hydraulic Presses

Standard Function Blocks

- Bit 06:

Valve acknowledgement input parameter

S2 remains low after

the valve is switched off
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

INFORMATION
If no reaction time has been set for switching off the valve
(

TOff = 0), Bit 06 will remain set on switch-off until the valve

returns to its start position. This is not a fault, but is important
to bear in mind.

- Bit 07:

Valve Y2 not in its start position (off) when switched on, i.e.
signal at input parameter

S2

=

0

Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 08:

Reset input constantly high, set too early, or

EIN = 1 or S1 = 0

or

S2 = 0

Remedy: Release reset button and press it again.
If this does not work, check switch, cable, input card and all
conditions and then reset (input parameter

RSET)

- Bit 09:

Valve acknowledgement input parameter

S2 goes to its start

position during operation (input parameter

S2 goes high while

output parameter

Y2 = 1)

Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 10:

Input parameter

StEn is not high when switching on via Y1On /

Y2On. This message disappears automatically as soon as
input parameter

StEn = 1. This is not an fault, but is important

to bear in mind.

- Bit 11:

Invalid combination:

Y1On = 1 and Y2On = 1

Remedy: Check switch, cable, input card and all conditions.
Check the software to ensure both valves cannot be driven
simultaneously (see 4-107 and 4-109) and then reset (input
parameter

RSET)

SB089