Modular Block System: Hydraulic Presses

Standard Function Blocks

SB072

Please note: In this case, the inverted signal from MP2 must be stored
in an auxiliary flag. This auxiliary flag should be assigned to input
parameter

MP2.

Example:
L

Exx.xx

(input to which sensor MP2 is connected)

=N

Myy.yy

(Auxiliary flag; must not be used elsewhere in the
program)

Please note:
The auxiliary flag must be reserved exclusively for this application and
must not be used elsewhere in the program. Not even interrupt
processing should be able to amend this flag.

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 00:

Synchronisation time for

NO_1/NO_2 (of the ESPE/AOPD)

exceeded
Remedy: Check ESPE/AOPD, cable, input card and all
conditions, then reset

- Bit 01:

NO_1 or NO_2 on ESPE/AOPD had not dropped out
Remedy: This error can only be cleared by a further
interruption to the ESPE/AOPD (function control), followed by
pressing the reset button (input parameter

RSET).

- Bit 02:

Simultaneous 0/1-pulse edge at input parameters

MS1 and

MS2, or input parameter MS2 = 1 during a 1/0-pulse edge at
input parameters

MP1 and MP2 and the ESPE/AOPD has not

been interrupted (MS2 “sticking”).
Remedy: Check muting inputs, cable, input card and all
conditions, and then reset.

- Bit 03:

Input parameter

MS1 or MS2 has changed, while input

parameter

Toff = 1

Remedy: Check ESPE/AOPD, cable, input card and all
conditions, and then reset.