Blocks required, Standard function blocks sb072 – Pilz PSS SB HYD, Basic license User Manual
Page 164

6-102
Modular Block System: Hydraulic Presses
Standard Function Blocks
SB072
- Bit 14:
RSet input constantly high or set too early
Remedy: Check switch, cable, input card and all conditions,
and then reset.
- Bit 15:
ESPE/AOPD is clear, confirm with
RSET.
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
- DW1001: Contact synchronisation time of 2 N/O contacts
(NO_1 and NO_2 of the ESPE/AOPD)
- DW1022: Minimum PSS scan time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
This manual is related to the following products:
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license