Monitoring muting lamps, Examples – Pilz PSS SB HYD, Basic license User Manual
Page 282

6-46
Examples
Modular Block System: Hydraulic Presses
24 V
Reset
Lamps
E33.00
PSS SB DI8O8
Muting
Lamp 2
A32.07
E32.05
Muting
Lamp 1
A32.06
E32.04
E32.07
E32.06
E32.03
E32.02
E32.01
E32.00
Muting sensor
A32.02 E32.04 A32.03
E32.05
0 V
24 V
AOPD
Muting
Lamp 1
Muting
Lamp 2
E33.01
Reset
Muting
Monitoring muting lamps
Blocks used: SB072/MUTING and SB097/MUT_LAMP
In this example, the ESPE/AOPD, muting sensor and muting lamps are
connected to the SafetyBUS p module PSS SB DI808. The muting lamps
can either be driven via the negative-switching outputs (A32.06 and
A32.07) or via the positive-switching outputs (A32.02 and A32.03) in
conjunction with optocouplers.
Fig. 8-24: Monitoring muting lamps
This manual is related to the following products:
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license