Examples – Pilz PSS SB HYD, Basic license User Manual
Page 280

8-44
Examples
Modular Block System: Hydraulic Presses
ESPE/AOPD in guard mode with automatic function test (SB069)
Block used: SB069/AOPD_GDO
Set operating mode:
The following operating mode is set for this application:
GRP
= M116.00 (SafetyBUS p I/O-Group 0)
GdOn = 1
ESPE/AOPD as guard function with
SSeq
= 0
start-up disabler/function test and
ARSt
= 0
reset lock
The signal may come from a connected operating mode
selector switch block (e.g. SB051).
Sequence of automatic function test of the ESPE/AOPD in guard
mode:
• A 0/1-pulse edge at the input parameter
Test requests an automatic
function test of the ESPE/AOPD.
• The output parameter
TEST (ESPE/AOPD emitter) is switched off.
• As soon as both input parameters
NO_1 and NO_2 (ESPE/AOPD-
outputs) show a 0-signal, the output parameter
TEST (ESPE/AOPD
emitter) will be switched back on again (
TEST = 1).
• The test is complete when both input parameters
NO_1 and NO_2
(ESPE/AOPD outputs) show a 1-signal again, i.e. switched on.
INFORMATION
The block enable output parameter
ENBL = 1 for the whole duration of the
automatic function test of the ESPE/AOPD.
The maximum permitted duration of the whole test on Type 2 ESPE/
AOPDs is 150 ms (in accordance with EN 61 496-1 Section 5.2.4, 06/98).
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license