Error messages – Pilz PSS SB HYD, Basic license User Manual
Page 75

Modular Block System: Hydraulic Presses
6-13
•
RSET:
Reset output
RSET = 1: The operating mode has been changed.
If the operating mode has been changed (e.g.
“reset ESPE/AOPD”), the
RSET output will be
high for one cycle.
Error messages
Any fault that is detected will be stored in the corresponding error data
word (
SSNR) of DB015 (1st data block), until the fault has been fully dealt
with.
• Error messages in DB015
- Bit 00:
Incorrect code from switch
Remedy: Check switch position
Otherwise: Check switch, cable and input card, then reset
(input parameter
RSet)
- Bit 01:
No signal from operating mode selector switch, both signals
interrupted
Remedy: Check switch
Otherwise: Check cable and input card, then reset
(input parameter
RSet)
- Bit 08:
Switch changed when
LOCK = 1
Remedy:
If switch has not changed: Check switch, cable and input card,
then reset (input parameter
RSet)
If switch has changed: Check switch position and then reset
(input parameter
RSet)
- Bit 14:
RSet input constantly high or set too early
Remedy:
If
RSet input was not set too early and is constantly high:
Check switch, cable and input card, then reset
(input parameter
RSet)
If
RSet input was set too early: reset again
(input parameter
RSet)
INFORMATION
Error bits 00, 01 and 08 can only be reset in “Setup” mode.
• Error messages on the CPU-display
- None
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license