Modular Block System: Hydraulic Presses

Safety gate monitoring with manual start and manual restart,
category 2

Block used: SB066/ST_K4

Cyclical function test on the gate:
The following application requires a cyclical function test of the safety gate
(open/close gate).
This requirement is met by carrying out a function test at appropriate
intervals using a 1/0-pulse edge at the input parameter

MEin.

Set operating mode:
The following operating mode is set for this application:

ARSt = 0: Reset lock activated (manual reset)

The operator has to reset each time the safety gate opens
(input parameter

Strt).

NFkT = 0

A function test is required. When the PSS is started up or
reset, the operator is forced to carry out a function test on
the gate before starting.

AuSt = 0

Start-up disabler activated (manual start)
The operator must reset each time the PSS is started up or
reset (input parameter

Strt).