Safety gate monitoring with manual start and manual restart,
category 2
Block used: SB066/ST_K4
Cyclical function test on the gate:
The following application requires a cyclical function test of the safety gate
(open/close gate).
This requirement is met by carrying out a function test at appropriate
intervals using a 1/0-pulse edge at the input parameter
MEin.
Set operating mode:
The following operating mode is set for this application:
ARSt = 0: Reset lock activated (manual reset)
The operator has to reset each time the safety gate opens
(input parameter
Strt).
NFkT = 0
A function test is required. When the PSS is started up or
reset, the operator is forced to carry out a function test on
the gate before starting.
AuSt = 0
Start-up disabler activated (manual start)
The operator must reset each time the PSS is started up or
reset (input parameter
Strt).
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license