6-84

Modular Block System: Hydraulic Presses

Standard Function Blocks

SB071

SB071: Initialisation of administration data blocks

Block header

Input parameters

CoSy:

Contact synchronisation time of 2 N/O or N/C contacts

RFbL:

Reaction time feedback loop contactor

CS_B:

Contact switchover time N/O / N/C on buttons

CS_R:

Contact switchover time N/O / N/C on relays

MaCy:

Machine cycle time for cycling ESPE/AOPD

ESPE:

ESPE/AOPD reaction time

Function

• Reads in the preset minimum scan time from DB002

A minimum scan time must always be configured if you are using MBS
blocks. Please refer to the section entitled “Minimum scan time” in
Chapter 5.

• Calculates the cycles using the times transferred in the parameters

• Enters the values into global parameters DW1001 ... DW1023 of the

administration data blocks.

SB071

INIT_MBS

B - CoSy
B - RFbL
B - CS_B
B - CS_R
W - MaCy
B - ESPE