Sb086: overrun control on linear-driven presses, Block header, Input parameters – Pilz PSS SB HYD, Basic license User Manual
Page 182: Standard function blocks, Sb086

6-120
Modular Block System: Hydraulic Presses
Standard Function Blocks
SB086: Overrun control on linear-driven presses
Block header
Input parameters
•
SSNR:
Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(See sections entitled “Administration data blocks DB015,
DB016 and DB017” and “Input parameter SSNR” in the
operating manual for the MBS block package).
•
RQST:
Signal to request an overrun measurement.
RQST = 0/1 pulse edge, request an overrun measurement.
The request will only be accepted if overrun measurement is
not currently running. Removing a request (
RQST = 0) made
during an overrun measurement will not affect how this
measurement is performed.
•
STRT:
Start signal to set the enable (“ENBL”). If no error is present,
the start signal is simply passed to the “ENBL” output until the
test cam (
TLS) is reached.
STRT = 0: No start signal is present; (stop overrun
measurement)
STRT = 0/1-pulse edge: Start overrun measurement
STRT = 1: Perform overrun measurement
SB086
OVERRUN
B - SSNR
X - RQST
X - STRT
X - ETP
X - TLS
W- MTi
X - RSET
ENBL -
X
OK
-
X
SB086
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license