Modular Block System: Hydraulic Presses

6-139

Function

• The valves can only be switched on if both valves are in their start

position (input parameter

S1 = 1 and S2 = 1, valve de-energised,

acknowledgement from the valves is present) and input parameter
Y1On = 1 and Y2On = 1.

• The valves can be switched off individually to enable external overrun

measurement.

Overrun measurement for Y1:

- Input parameter Y1On and Y2On = 1

- Switch on valves via input parameter

ON

- Switch off valve Y1 via input parameter

Y1On = 0 to enable overrun for

Y1 to be measured

- Switch off valve Y2 via input parameter

ON = 0

Overrun measurement for Y2:

- Input parameter Y1On and Y2On = 1

- Switch on valves via input parameter

ON

- Switch off valve Y2 via input parameter

Y2On = 0 to enable overrun for

Y2 to be measured

- Switch off valve Y1 via input parameter

ON = 0

• Key to settings at

Y1On and Y2On

Y1On = 0

Y1On = 1

Y2On = 0

Invalid combination

Overrun measurement

Error

Y2 switched off

Y2On = 1

Overrun measurement

Normal

Y1 switched off

working mode

• In order to detect shorts, valve Y2 is switched on one PSS-cycle after

valve Y1.
Both valves are switched off simultaneously.

• Monitors position through acknowledgement of the valves' position (input

parameters

S1 and S2) within a maximum reaction time. The reaction

time for switch on and switch off may be selected individually.

- Reaction time when switching on the valve:

When switched on, the valves must leave their start position within a