Function – Pilz PSS SB HYD, Basic license User Manual
Page 201

Modular Block System: Hydraulic Presses
6-139
Function
• The valves can only be switched on if both valves are in their start
position (input parameter
S1 = 1 and S2 = 1, valve de-energised,
acknowledgement from the valves is present) and input parameter
Y1On = 1 and Y2On = 1.
• The valves can be switched off individually to enable external overrun
measurement.
Overrun measurement for Y1:
- Input parameter Y1On and Y2On = 1
- Switch on valves via input parameter
ON
- Switch off valve Y1 via input parameter
Y1On = 0 to enable overrun for
Y1 to be measured
- Switch off valve Y2 via input parameter
ON = 0
Overrun measurement for Y2:
- Input parameter Y1On and Y2On = 1
- Switch on valves via input parameter
ON
- Switch off valve Y2 via input parameter
Y2On = 0 to enable overrun for
Y2 to be measured
- Switch off valve Y1 via input parameter
ON = 0
• Key to settings at
Y1On and Y2On
Y1On = 0
Y1On = 1
Y2On = 0
Invalid combination
Overrun measurement
Error
Y2 switched off
Y2On = 1
Overrun measurement
Normal
Y1 switched off
working mode
• In order to detect shorts, valve Y2 is switched on one PSS-cycle after
valve Y1.
Both valves are switched off simultaneously.
• Monitors position through acknowledgement of the valves' position (input
parameters
S1 and S2) within a maximum reaction time. The reaction
time for switch on and switch off may be selected individually.
- Reaction time when switching on the valve:
When switched on, the valves must leave their start position within a
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license