- Bit 08:
Protected field broken
Remedy: Clear protected field, reset if necessary
Otherwise: Check ESPE/AOPD outputs, cable, input card and
all conditions and then reset (input parameter
RSET)
- Bit 09:
Start-up disabler
Remedy: Carry out a function test on the ESPE/AOPD (break
protected field and then clear) and then reset (input parameter
RSET)
- Bit 10:
I/O-Group stop triggered while PSS is in normal RUN mode
Remedy: Start I/O-Group
• Error messages on the CPU-display
- E003:
Administration data block has not been initialised
Remedy: Call SB071 in OB120
Global parameters used in the administration data blocks
Global parameters may be set in OB120 using SB071.
• DW1001:
Number of cycles in the contact synchronisation time
between two N/O or N/C contacts
• DW1022:
Minimum scan time
Blocks required
• DB015, DB016, DB017:
Administration data blocks
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
• SB071
Initialisation of global parameters in DB015, DB016 and DB017
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license