Blocks required, Standard function blocks, Sb059 – Pilz PSS SB HYD, Basic license User Manual
Page 84

6-22
Modular Block System: Hydraulic Presses
Standard Function Blocks
- Bit 09:
Button pressed without start enable
Remedy: Check enable input, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 10:
Synchronisation time error, T1 missing (no “Auf” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 11:
Synchronisation time error, T2 missing (no “Auf” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 12:
Two-hand control RESET via
MEin (button released)
Remedy: Check switch, cable, input card and all conditions,
then reset (input parameter
RSET)
- Bit 14:
T1 not released (no “Jog” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
- Bit 15:
T2 not released (no “Jog” mode)
Remedy: Check input button, cable, input card and all
conditions, then reset (input parameter
RSET)
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1022: Minimum scan time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
SB059
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license