Output parameters – Pilz PSS SB HYD, Basic license User Manual
Page 103

Modular Block System: Hydraulic Presses
6-41
•
TFbL:
Time for feedback loop monitoring when switching on/off
Permitted value range in ms: 0 ... 2000
When
TFbL = 0, the default value for feedback loop monitoring
will be used from DW1002 of the administration data block
(global parameter
RFbL).
Format: Word constants KF000000 ... KF002000
Recommended value: 100 ms (KF000100)
INFORMATION
The value for feedback loop monitoring should be less than the interval
between consecutive operations.
Irrespective of parameter
TFbL, the initial acknowledgements from
feedback loops
FbL1 =1 and FbL2 = 1 must always be present when
switching on (ON = 0/1 pulse edge).
•
RSET:
Reset input
RSET = 0/1 pulse edge: trigger reset
Input circuitry
If you are only using one feedback loop, connect the feedback loop input
to
FbL1 and FbL2.
Output parameters
•
ENBL:
Enable bit
ENBL = 0: Enable is blocked
ENBL = 1: Contactors are free from error
•
K1:
Output for driving contactor 1
•
K2:
Output for driving contactor 2
Output circuitry
If you are only using one contactor, connect the contactor output to
K1 and
K2.
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license