Modular Block System: Hydraulic Presses

6-89

MS2:

N/O contact of Muting signal Serial 2
MS2 = 0:

Not operated (muting signal off)

MS2 = 1:

Operated (muting signal on)

MP1:

N/O contact of Muting signal Parallel 1
MP1 = 0:

Not operated (muting signal off)

MP1 = 1:

Operated (muting signal on)

MP2:

N/O contact of Muting signal Parallel 2 or (inverted) N/C
contact with sensors (please refer to “Safety guidelines” in the
SB description)
MP2 = 0:

Not operated (muting signal off)

MP2 = 1:

Operated (muting signal on)

TS12:

Time Sequential
This setting determines the maximum time that can elapse
between the operation (0/1-pulse edge) of MS1 and MS2.
Permitted value range: 0 ... 32 767
Format:

Word

Time unit:

ms

TPSy :

Timer Parallel Synchronisation
This setting determines the maximum time (synchronisation
time) that can elapse between the operation (0/1-pulse edge)
of MP1 and MP2.
Permitted value range: 0 ... 2047
Format:

Word

Time unit:

ms

TInt:

Timer Interrupt
This setting determines:
- the maximum permitted release time of the ESPE/AOPD or
- the maximum interrupt time of MP1 or MP2

during active

muting
Permitted value range: 0 ... 2047
Format:

Word

Time unit:

ms

While muting is activated in sequential mode and
MS2 = MP1 = 1 (MS1 and MP2 irrelevant), the ESPE/AOPD
may be released without the muting function being switched
off (e.g. during gaps in the load). If only MS2 = 1 (MP1 = 0,
MS1 and MP2 irrelevant), the ESPE/AOPD may only be
released for the time stated under

TInt.

Sequential muting will be switched off when