Error messages, Standard function blocks sb097 – Pilz PSS SB HYD, Basic license User Manual
Page 230

6-168
Modular Block System: Hydraulic Presses
Standard Function Blocks
SB097
Error messages
Any fault that is detected will be stored in the corresponding error data
word (
SSNR) of DB015 (1st data block), until the fault has been fully dealt
with.
• Error messages in DB015
- Bit 00:
Broken filament, wiring error or optocoupler fault on muting
lamp 1
Remedy:
Change muting lamp, then reset. If the error is still present:
Check the cabling, then reset. If the error is still present and an
optocoupler has been used:
Check the optocoupler, then reset
- Bit 01:
Broken filament, wiring error or optocoupler fault on muting
lamp 2
Remedy:
Change muting lamp, then reset. If the error is still present:
Check the cabling, then reset. If the error is still present and an
optocoupler has been used:
Check the optocoupler, then reset
- Bit 02:
Fault on logic element of muting lamp 1 (e.g. defective
optocoupler)
Remedy:
Check cabling, then reset. If the error is still present:
Check the optocoupler and output module, then reset
- Bit 03:
Fault on logic element of muting lamp 2 (e.g. defective
optocoupler)
Remedy:
Check cabling, then reset. If the error is still present:
Check the optocoupler and output module, then reset
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license