Blocks required – Pilz PSS SB HYD, Basic license User Manual
Page 115

Modular Block System: Hydraulic Presses
6-53
- Bit 14:
Strt input constantly high or set too early
Remedy: If
Strt input was not set too early and is constantly
high: Check switch, cable and input card, then reset (input
parameter
Strt).
If
Strt input was set too early: reset again
(input parameter
Strt)
- Bit 15:
Gate closed,
Strt signal is missing
Remedy: Check all conditions and then reset
(input parameter
Strt)
• Error messages on the CPU-display
- None
Global parameters used in administration data block DB015
Global parameters may be set in OB120 using SB070.
• DW1022: Minimum scan time
Blocks required
• DB015:
Administration data block
DB015 must consist of its total length of 1024 data words.
DB015 must have READ/WRITE access.
• SB070
Initialisation of global parameters in DB015
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license