Modular Block System: Hydraulic Presses
INFORMATION
Input circuitry:
• To achieve category 4, two independent shutdown routes must be
provided within the current path of the potentially dangerous drive
• If wiring is to be laid outside the control cabinet, feedback loops must use
test pulses.
• Feedback loops must use test pulses if the possibility of a short-circuit
cannot be excluded.
• If only one contactor is used to switch a potentially dangerous drive, it
must be possible to switch this off via a group contactor within the
current path (selective shutdown).
• The group contactor must also be monitored through a feedback loop.
SB066: Safety gate monitoring
SB066 is designed for monitoring a safety gate. It can monitor a safety
gate with one or two switches.
SB066 meets all the requirements of category 4, in accordance with
EN 954-1, 03/97.
Operating modes:
• Automatic restart
• Automatic start when PSS starts up
Start-up reset when PSS is cold-started
• No function test on the gate
(function test = opening and closing the gate)
INFORMATION
Input circuitry:
• Inputs should have pulsed outputs
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license