Pilz PSS SB HYD, Basic license User Manual
Page 135

Modular Block System: Hydraulic Presses
6-73
•
MTD:
Maximum permitted duration of the whole automatic function
test of the ESPE/AOPD
Permitted value range: 0 ... 255 ms
With type 2 ESPE/AOPDs, EN 61 496-1 specifies that the
maximum permitted duration of the complete test is 150 ms.
•
SSeq:
The input parameter
SSeq establishes the start-up procedure
at a PSS cold or warm start, when the SafetyBUS I/O-Group
starts up or at a 0/1-pulse edge at the input parameter
GdOn.
SSeq = 0:
No automatic start-up (start-up disabler)
Function test required (please refer to “Function”)
SSeq = 1:
No automatic start-up (start-up disabler)
No function test required
Reset required (input parameter
RSET)
INFORMATION
SSeq = RLO-0 (M110.00) must be set on presses.
•
ARSt:
Automatic restart after fault “Protected field interrupted” once
the protected field is clear.
ARSt = 0:
No automatic reset after fault “Protected field
interrupted” once the protected field is cleared,
i.e. a reset signal is required once the protected
field is broken (reset lock).
ARSt = 1:
Automatic reset after fault “Protected field
interrupted”
•
Test:
Test input (simulating a break in the protected field)
Test = 0/1-pulse edge: A test cycle is started.
The output parameter
TEST is set at “0”, i.e. the
ESPE/AOPD emitter is switched off.
For example, the enable or “
OT” signal should be
connected to this parameter.
•
RSET:
Reset button (N/O contact)
RSET = 0/1-pulse edge: Reset occurs
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license